Products Categories

Switchgear

Multi-bay and load-interrupter switches for a range of applications

Pad-mounted switchgear

Rucker switchgear comes in pad-mounted and metal-enclosed configurations for your padmount or unit substation transformer.

Product Details

Description

  • 15 kV double-door design
  • Up to 4 bays
  • Multiple switch and fuse configurations available
  • UL listed
  • Meets or exceeds IEEE C37.74
  • Munsell Green hi-gloss finish suitable for heavy-duty applications
  • Ideal for publicly accessible outdoor installations
  • Low-profile
  • Tamper-proof
  • Lockable

Standard specs

  • Nominal: 14.4 kV
  • Maximum design: 15.5 k
  • VBIL: 95 kV
  • Main bus continuous: 600 amps
  • Load interrupting: 600 amps
  • Short-circuit
  • RMS symmetrical: 25 kA3-time duty cycle fault closing
  • RMS asymmetrical: 40 kA
  • Frequency: 60 hertz
  • Maximum altitude: 3300 feet
  • Fuse unit: type DBU, 15 kV, standard speed (E)

Optional upgrades

  • Live-front designs
  • 6 compartment option (up to 5 switch and 5 fuse arrangements)
  • 25 kV designs
  • DBU fuse speed variations: slow “E” and “K”

Description

  • 5/15 kV
  • General purpose switches
  • Current-limiting clip-lock fusing options (up to 600E for 5 kV applications and up to 300E for 15 kV applications)
  • Optional close-couple kit
  • UL listed and CSA approved
  • Meets or exceeds IEEE C37.20.3
  • 11-gauge steel construction
  • ANSI 61 gray powder coating for a durable, lasting finish

Standard specs

  • Maximum rated voltage: 15 kV
  • Main bus continuous: 600
  • AmpsFault close asymmetrical: 40 kA
  • Momentary switch closed asymmetrical: 40 kA
  • 2 second short-time Current RMS symmetrical: 25 kA
  • BIL: 95 kV
  • Space heater circuit w/ thermostat (requires 120 VAC external power source)
  • Provision for kirk key interlock
  • Mechanism and contacts: copper-silver plated
  • Frequency: 60 hertz
  • Maximum altitude: 3300 feet
  • Line terminals: ANSI segment 3
  • Load terminals: ANSI segment 1
  • Enclosure: NEMA 3R, outdoor/indoor

Optional upgrades

  • 27 kV designs
  • Dry-contact kit (2 normally open, 2 normally closed)
  • Customer metering
  • Multi-bay lineups
  • Surge arresters
  • Convenience light
  • Space heater switch
  • Duplex receptacle
  • Run back bus

Releted Products